Introduction

1  collector  array 
1  storage  tank  
1  pump  and  auxiliary  heating  Description:

The  solar  circuit  pump  (R1)  is  switched  on  as  soon  as  the  switch on  
temperature difference  (△Ton)  between  the  collector  array  (T1)  and  the  
storage  tank  (T2)  is  reached.  If  the  temperature  difference  between  
the  collector  array  (T1)  and  storage tank  (T2)  drops  below  the  switch off  temperature  difference  (△Toff),  or  the  temperature  of  storage  tank  
(T3)  reaches  the  preset  maximum  storage  temperature,   then  the  solar  
circuit  pump  (  R1)  is  switched  off.  Back up  heating  by  auxiliary  boiler  
(detailed  see  paragraph  4.3):  Within  the  preset  time  section  of  back-up  
heating,  if  the  temperature  T3  is  below  the  switch-on  temperature,  
then  the  circulation  pump  (H1)  of  back-up  heating  is  triggered,  when  
T3  is  heated  to  the  switch-off  temperature,  circulation  pump  H1  of  back-up  
heating  is  ceased.

Technical Data

Specification   SR868C8Q   SR868C8
Appearance  of  controller
120mm×120mm×18mm
120mm×120mm×18mm 
Power  supply
AC230V±10%
AC230V±10% 
Power  consumption 
<  3W 
 <  3W
Accuracy  of  temperature measuring 
±2oC 
 ±2oC 
Range  of  collector
-10~220oC 
-10~220oC 
Range  of  tank temperature  measuring
0~110oC
0~110oC
Suitable  power  of  pump
three  pumps,≤ 600W 
three  pumps,≤  600W

Suitable  power  of
electrical  heater

 power≤ 1500W
power≤ 1500W
Inputs
2pcs x Pt1000 sensor  
(≤500oC)
 1 x Pt1000 sensor  
(≤500oC)
 
collector (silicon  cable≤280oC),
for collector  
(silicon  cable≤280oC),
 
3pcs x NTC10K, B3950  
sensor
2 x NTC10K, B3950 sensor
 
(≤135oC) for tank(PVC cable ≤105oC)
(≤135oC) for tank,(PVC cable ≤105oC)
Outputs
3 relays, for circulation  
pumps
3 relays, for circulation  
pumps
 
or 3-way electromagnetic  
valve
or  3-way electromagnetic valve
 
1 relay for electrical heater
1 relay for electrical  
heater
Ambient  temperature
-10~50  oC
-10~50  oC
Water  proof  grade
 IP40 
  IP40 

                                                                  

Main Functions

1.Main  menu  DT  O  &  DT  F  Temperature  difference  function
2.Main  menu-THET  timing  heating
3.TEMP  Temperature  main  menu
4.EM  Emergency  collector  temperature
(emergency  switch-off  temperature  of  collector)
5.CMX  Maximum  limited  collector  temperature  (collector  cooling  function)
6.CMN  low  temperature  protection  of  collector
7.CFR  frost  protection  of  collector
8.SMX  Maximum  temperature  of  tank
9.REC  Tank  re-cooling  function
10.Celsius  and  Fahrenheit  temperature  transferring
11.FUN  Auxiliary  function
12.DVWG  Anti-Legionella  function
13.CIRC  Temperature  controlled  hot  water  circulation  pump
14.nMIN  Solar  circulation  pump  speed  adjusting  (RPM  speed  controlling)
(Only  available  on  SR868C8Q)
15.OHQM  Thermal  energy  measuring  (Only  available  on  SR868C8Q)
16.INTV  Pump  interval  function      (Only  available  on  SR868C8Q)
17.BYPR  High  temperature  by-pass  function
(tank  temperature  automatically  adjusting)
18.  HND  Manual  mode
19.PASS  Password  setting
20.LOAD  Recovery  to  factory  setting
21.ON/OFF  button
22.Holiday  function
23.Manual  heating
24.Temperature  query  function
25.Memory  Protection
26.Anti-dry  heating  Protection